Bathroom Electrical Code Cheat Sheet (NEC 2023)

GFCI on every outlet, the 36-inch sink receptacle rule, 20 A circuits, and fan and light placement, with NEC section numbers, a GFCI checker and a circuit planner.

Last reviewed against NEC 2023, reviewed October 2026. Your town may be on an older edition or add local amendments; check with the building department.

GFCI requirements: does it need GFCI?

Every bathroom receptacle needs GFCI protection, at any distance from the sink (NEC 210.8(A)(1)). The 6 ft rule is for sinks in other rooms.
NEC edition
GFCI
If the maker requires it
AFCI
Not required by the NEC in bathrooms; check local amendments
Code
NEC 410.10(D), 110.3(B)
Use a fan listed for installation over a tub or shower. Most of them require a GFCI-protected circuit in their instructions.

GFCI type and height

  • GFCI receptacle first on the run protects everything downstream; a GFCI breaker protects the whole circuit; a dead-front GFCI adds protection with no outlet.
  • No NEC minimum height: within 36 in. of the basin and no more than 12 in. below the countertop.
  • A 15 A receptacle is allowed on the 20 A circuit when there are two or more receptacles; a single receptacle must be 20 A.

Outlet placement and the code at a glance

Tub3 ft out, 8 ft up: no hanging fixturesBasinGFCI within 36 in.Switch at the doorFanDuct outside
Plan view, not to scale.
RuleRequirementNEC / IRC
GFCI on every bathroom receptacleAt any distance from the sink; GFCI receptacle, dead-front or GFCI breaker210.8(A)(1)
Receptacle at each basinAt least one within 36 in. of the outside edge of each basin, on the wall or partition beside it, no more than 12 in. below the countertop210.52(D)
Bathroom receptacle circuitAt least one 20 A circuit for bathroom receptacles; it may also feed the lights and fan of a single bathroom210.11(C)(3)
No receptacle in the tub or showerNo receptacle within or directly over the tub or shower stall406.9(C)
Tamper-resistant receptaclesAll 15 and 20 A, 125 V receptacles in a dwelling406.12
Fixtures near the tubNo hanging fixtures, track lights, pendants or ceiling fans within 3 ft horizontally and 8 ft vertically of the tub rim or shower threshold410.10(D)
Damp and wet ratingsDamp-rated fixtures in the bathroom; wet-rated where subject to shower spray410.10(A)
Switched lightingAt least one wall-switch-controlled light; the switch at the entry210.70(A)(1)
Ventilation50 CFM intermittent or 20 CFM continuous, ducted outdoors; a 1.5 sq ft openable window may substitute where allowedIRC R303.3, M1505
AFCINot required in bathrooms by the NEC through 2023; some states and cities add it210.12(A)

Circuits and amps: one 20 A circuit or more?

One 20 A circuit works

Fixed loads are 1.3 A, within the 10 A allowed with receptacles on the same 20 A circuit, and nothing else in the house is on it (NEC 210.11(C)(3) exception).

  • Receptacles, lights and fan (this bathroom only): 20 A, 12 AWG, GFCI

Fixed loads 1.3 A plus a 1,500 W hair dryer (12.5 A) = 13.8 A at peak.

Save this plan to your bathroom remodel in Blueprint: the circuits, the GFCI result for each device, the shopping list and the rough-in and final inspections, on your phone for the store and the inspector.

Project plan · built from your numbers

Wire a bathroom on one 20 A circuit

Fixed loads are 1.3 A, within the 10 A allowed with receptacles on the same 20 A circuit, and nothing else in the house is on it (NEC 210.11(C)(3) exception). GFCI on every receptacle (NEC 210.8(A)(1)), one within 36 in. of each basin, and no hanging fixtures within 3 ft and 8 ft of the tub.

Materials
$180
Time
1 to 2 weekends
Level
Advanced
6 steps 5 tools 6 materials
  1. 1

    Pull the permit

    New bathroom circuits, fans and lights are usually permitted work. Many places allow a homeowner permit for their own house.

    • Permit issued
    • Rough-in inspection booked
  2. 2

    Lay out devices

    Mark a receptacle within 36 in. of each basin, the switch at the door and the fan away from the shower unless it is listed for it.

    • Receptacle within 36 in. of each basin
    • Nothing within or over the tub or shower
    • No hanging fixtures within 3 ft and 8 ft of the tub
  3. 3

    Run the circuits

    Fixed loads are 1.3 A, within the 10 A allowed with receptacles on the same 20 A circuit, and nothing else in the house is on it (NEC 210.11(C)(3) exception).

    • Receptacles, lights and fan (this bathroom only): 20 A, 12 AWG
01 · Your numbers
Circuits
1
Fixed load
1.3 A
GFCI
Every receptacle
Fan
0.8 A
02 · The plan

6 steps · 5 tools · 6 materials

3 more steps, the full tool list and a shopping list you can check off as you go.

03 · Finished

Your plan is 60% built. Save it.

3/5

Wire a bathroom on one 20 A circuit

Finished in 1 to 2 weekends · $180 DIY

Built for your circuits of 1. Your first plan saves free. No card needed.

Or save it with just your email

We send a link; open it and this plan is your first project. Your first plan saves free. No card needed.

FanTypical amps
50 to 80 CFM quiet fan0.2 to 0.6 A
100 to 150 CFM fan0.6 to 1.5 A
Fan and light combo1 to 2 A (with LED)
Fan, light and heater combo10 to 13 A (1,300 to 1,500 W heater)

Check wire size on long runs with the voltage drop calculator and the panel with the electrical load calculator.

Lights and fans

FixturePlacementRating
Vanity sconces60 to 66 in. to center, either side of the mirrorDamp
Vanity barAbove the mirror, about 78 in. off the floorDamp
Shower or tub lightRecessed or close-to-ceiling, never hanging within 3 ft and 8 ft of the tubWet if exposed to spray
Exhaust fanNear the shower or toilet, ducted outdoors (never into the attic)Listed for over a tub if placed there

Wall switches for lights and fans go outside the tub and shower space; a timer or humidity switch keeps the fan running long enough to clear the moisture.

Ventilation

The IRC requires 50 CFM intermittent or 20 CFM continuous exhaust, ducted outdoors (M1505), unless an openable window of at least 1.5 sq ft is allowed instead (R303.3). For comfort, size the fan at 1 CFM per square foot in baths up to 100 sq ft, or 50 CFM per toilet, shower and tub (100 for a jetted tub) in larger rooms.

Use 4 in. duct for runs up to about 25 ft and 6 in. beyond, insulated where it crosses an unheated attic.

Permits

New bathroom circuits, fans and lights are usually permitted, with a rough-in inspection before drywall and a final. See the permit and inspection guide, and compare rooms in the bedroom, kitchen and garage electrical sheets.
Outside the US: UK and IEC bathroom zones 0 to 2

The zone system belongs to BS 7671 and IEC 60364-7-701, not the NEC.

  • Zone 0: inside the bath or shower tray; SELV 12 V equipment rated IPX7.
  • Zone 1: above the bath or tray to 2.25 m; IPX4 at least.
  • Zone 2: 0.6 m beyond zone 1; IPX4 at least. Pull-cord switches or switches outside the room.

Frequently asked questions

Do bathroom lights need to be GFCI protected?

Not by the NEC. GFCI is required on bathroom receptacles (210.8(A)(1)). A light in the tub or shower space needs GFCI only if its instructions say so, which many recessed shower trims do.

Does a bathroom exhaust fan need GFCI?

Not by the NEC for a fan outside the tub area. A fan installed over a tub or shower must be listed for that spot, and most of those require a GFCI-protected circuit in their instructions (110.3(B)).

What size GFCI for a bathroom?

A 20 A GFCI receptacle on the required 20 A bathroom circuit with 12 AWG wire. A 15 A GFCI receptacle is also allowed on a 20 A circuit when there is more than one receptacle on it.

How high should a bathroom GFCI outlet be?

The NEC sets no height. It must be within 36 in. of the basin and no more than 12 in. below the countertop (210.52(D)); about 42 to 44 in. off the floor, or 4 to 8 in. above the countertop, is typical.

Can bathroom lights and outlets share a circuit?

Yes, if the 20 A circuit serves only that one bathroom (210.11(C)(3) exception). Otherwise the receptacle circuit can serve several bathrooms but nothing else, and the lights go on another circuit.

How many amps does a bathroom fan use?

Most 50 to 150 CFM fans draw 0.2 to 1.5 A. Fan and light combos run 1 to 2 A with LEDs, and a fan with a built-in heater 10 to 13 A, which needs its own circuit.

Do I need a permit for bathroom electrical work?

Usually, for new circuits, a new fan or new fixtures. Like-for-like swaps of a receptacle or fixture often need none. Many places let a homeowner pull a permit for their own house.

Can I put an outlet inside a vanity or drawer?

A receptacle inside a cabinet does not count as the required one within 36 in. of the basin, and it still needs GFCI. Listed in-drawer outlets are allowed when installed to their instructions.

Permit check

Usually needs a permit

New bathroom circuits, fans and lights are usually permitted.

Inspections: Rough-in, then Final

Job checklist

0 of 8 done

Save it to a project

Ticks are saved in this browser. A project keeps them on every device.

Code changes

Get an email when the NEC changes this sheet

Model codes update every three years, and the parts that move this sheet are GFCI coverage, fan circuits and fixture zones. Leave an email and we will tell you when we update it for a new code cycle.

Local code notes for your county

Cities and counties amend the NEC, and the amendments are what inspectors fail people on. Tell us where the job is and your project gets the notes that apply there.

Questions about this sheet

Ask about your situation. Posting needs a free account, and your question carries over so you get an answer with your project in view. Questions we hear often get answered on this sheet.

Start a project

What are you building?

Pick one for a step-by-step plan with tools, materials and costs, or tell us in your own words.