Add up conductors, devices, clamps and grounds to find the box volume to check against.
Turn these numbers into a build plan.
Check the volume stamped in your box. Raised covers and extension rings add their marked volume. Turn the power off and test before opening a box.
Checked against NEC (NFPA 70) 2023, section 314.16. These rule values have not been reviewed by a licensed professional. Your local code and inspector decide, so verify with your building department.
Finished the electrical box fill? Snap a before and after. The photo maker lines them up into one image you can post, and a free Blueprint account keeps the photos with your measurements and materials.
Fit a box checked against the 14.0 cu in this wiring needs. Verify with your building department before you start.
Check permit needs
Ask your building department whether this work needs a permit or a licensed electrician.
Shut off and test
Turn off the breaker and test each conductor before touching anything.
Remove the old box
Disconnect the device, label the wires and remove the box.
5 steps · 4 tools · 2 materials
2 more steps, the full tool list and a shopping list you can check off as you go.

Your plan is 60% built. Save it.
3/5Replace an electrical box, 14.0 cu in needed
Finished in 1 afternoon · $15 DIY
Built for your box volume of 14.0 cu in. Your first plan saves free. No card needed.
Or save it with just your email
We send a link; open it and this plan is your first project. Your first plan saves free. No card needed.
Counting rules follow NEC (NFPA 70) 2023, section 314.16. Check your local amendments and the volume stamped in your box.
| Wire | Volume |
|---|---|
| 6 AWG | 5 cu in |
| 8 AWG | 3 cu in |
| 10 AWG | 2.5 cu in |
| 12 AWG | 2.25 cu in |
| 14 AWG | 2 cu in |
| 16 AWG | 1.75 cu in |
| 18 AWG | 1.5 cu in |
| Box | Volume |
|---|---|
| 3 x 2 x 2-1/2" metal device box | 12.5 cu in |
| 4" octagon x 1-1/2" metal | 15.5 cu in |
| Single-gang plastic, 18 cu in | 18 cu in |
| 3 x 2 x 3-1/2" metal device box | 18 cu in |
| Single-gang plastic, 20.3 cu in | 20.3 cu in |
| 4" square x 1-1/2" metal | 21 cu in |
| 4" octagon x 2-1/8" metal | 21.5 cu in |
| Single-gang plastic, 22.5 cu in | 22.5 cu in |
| 4-11/16" square x 1-1/2" metal | 29.5 cu in |
| 4" square x 2-1/8" metal | 30.3 cu in |
| Two-gang plastic, 34 cu in | 34 cu in |
| 4-11/16" square x 2-1/8" metal | 42 cu in |
| Three-gang plastic, 54 cu in | 54 cu in |
| Four-gang plastic, 68 cu in | 68 cu in |
Volumes are nominal. Check the marking inside your box. See the electrical cheat sheet and the voltage drop calculator.
Voltage drop and wire size for 120V, 240V, 3-phase and low-voltage DC runs
Calculate residential electrical service requirements using NEC methods
Liquid and suction line sizes, extra charge per foot and a chart for R-410A, R-32 and R-454B
Wire gauges, circuit breaker sizes, electrical codes, and safety guidelines
Visual guide identifying standard North American plug configurations and their usage
NEC 2023 bathroom rules with section numbers, a does-it-need-GFCI checker and a one-or-more circuit planner