Find the right wire size for any run, from a 12V landscape light to a 240V subpanel.
Length is one way, from the panel or transformer to the load. The calculator counts the return conductor.
Voltage drop
7.72 V (6.43%)
112.28 V at the load.
VD = 2 x I x L x R / 1000
= 2 x 20.0 A x 100 ft x 1.93 ohm/kft / 1000 = 7.72 V
% = 7.72 / 120 x 100 = 6.43%
Take this wire list to the store: Blueprint saves the circuit, the wire footage, breaker and conduit, and the steps.
Save this circuit to a project planSizing the whole panel? Electrical load calculator. Solar arrays: solar calculator.
Turn these numbers into a build plan.
Finished the voltage drop? Snap a before and after. The photo maker lines them up into one image you can post, and a free Blueprint account keeps the photos with your measurements and materials.
20 A at 120 V over 100 ft one way. 8 AWG copper keeps the drop near 2.5%. Pull a permit; most areas require one for a new circuit, and an inspector checks the wire size and breaker.
Confirm the load
Check the nameplate amps or watts. This plan uses 20.0 A.
Plan the route
Measure the actual path, not the straight line. Every extra foot adds drop; this plan allows 111 ft.
Get the permit
Most jurisdictions require a permit and inspection for a new circuit or subpanel feed.
7 steps · 4 tools · 4 materials
4 more steps, the full tool list and a shopping list you can check off as you go.

Your plan is 60% built. Save it.
3/5Run a 30 A circuit 100 ft on 8 AWG copper
Finished in 1 weekend plus inspection · $558 DIY
Built for your wire of 8 AWG copper. Your first plan saves free. No card needed.
Or save it with just your email
We send a link; open it and this plan is your first project. Your first plan saves free. No card needed.
Single-phase and DC: VD = 2 x K x I x L / CM. Three-phase: VD = 1.732 x K x I x L / CM. K is the resistance of a circular-mil foot of wire: 12.9 for copper and 21.2for aluminum. CM is the wire's area in circular mils (12 AWG is 6,530, 6 AWG 26,240). The calculator uses the Table 8 resistance directly, which gives the same answer.
NEC 210.19(A) Informational Note No. 4 suggests a branch circuit drop of 3% or less and 5% for feeder plus branch circuit combined. 215.2 says the same for feeders. They are informational notes, so they are not enforced unless your jurisdiction adopts them, but equipment makers design around them: motors run hot and EV chargers slow down on low voltage.
| Load | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 2 AWG |
|---|---|---|---|---|---|---|---|
| 15 A, 120 V | 39 ft | 62 ft | 99 ft | 157 ft | 244 ft | 389 ft | 618 ft |
| 20 A, 120 V | too small | 46 ft | 74 ft | 117 ft | 183 ft | 292 ft | 463 ft |
| 30 A, 120 V | too small | too small | 49 ft | 78 ft | 122 ft | 194 ft | 309 ft |
| 40 A, 120 V | too small | too small | too small | 58 ft | 91 ft | 146 ft | 231 ft |
| 50 A, 120 V | too small | too small | too small | too small | 73 ft | 116 ft | 185 ft |
| 60 A, 120 V | too small | too small | too small | too small | too small | 97 ft | 154 ft |
| Load | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 2 AWG |
|---|---|---|---|---|---|---|---|
| 15 A, 240 V | 78 ft | 124 ft | 198 ft | 314 ft | 488 ft | 779 ft | 1237 ft |
| 20 A, 240 V | too small | 93 ft | 148 ft | 235 ft | 366 ft | 584 ft | 927 ft |
| 30 A, 240 V | too small | too small | 99 ft | 157 ft | 244 ft | 389 ft | 618 ft |
| 40 A, 240 V | too small | too small | too small | 117 ft | 183 ft | 292 ft | 463 ft |
| 50 A, 240 V | too small | too small | too small | too small | 146 ft | 233 ft | 371 ft |
| 60 A, 240 V | too small | too small | too small | too small | too small | 194 ft | 309 ft |
12 AWG copper: 2 x 20 x 100 x 1.93 / 1000 = 7.72 V, or 6.4%. That fails 3%; 8 AWG drops 2.5%.
6 AWG copper drops 3.1%. The 3% size is 4 AWG. See the EV charger installation guide.
2 AWG copper drops 1.9%; 1/0 aluminum drops 2.0% and usually costs about half as much. Wiring the garage itself is covered in the garage electrical guide.
8.3 A on 12 AWG drops 2.57 V (21.4%); 10 AWG gets it to 13.4%. Valve wiring for a sprinkler system and 12 V recessed lighting follow the same math.
| Size | mm² | Circular mils | Copper (ohm/kft) | Aluminum (ohm/kft) | Ampacity Cu 60/75 C |
|---|---|---|---|---|---|
| 18 AWG | 0.82 | 1,620 | 7.77 | 12.8 | n/a |
| 16 AWG | 1.31 | 2,580 | 4.89 | 8.05 | n/a |
| 14 AWG | 2.08 | 4,110 | 3.07 | 5.06 | 15 / 20 A |
| 12 AWG | 3.31 | 6,530 | 1.93 | 3.18 | 20 / 25 A |
| 10 AWG | 5.26 | 10,380 | 1.21 | 2 | 30 / 35 A |
| 8 AWG | 8.37 | 16,510 | 0.764 | 1.26 | 40 / 50 A |
| 6 AWG | 13.3 | 26,240 | 0.491 | 0.808 | 55 / 65 A |
| 4 AWG | 21.2 | 41,740 | 0.308 | 0.508 | 70 / 85 A |
| 3 AWG | 26.7 | 52,620 | 0.245 | 0.403 | 85 / 100 A |
| 2 AWG | 33.6 | 66,360 | 0.194 | 0.319 | 95 / 115 A |
| 1 AWG | 42.4 | 83,690 | 0.154 | 0.253 | 110 / 130 A |
| 1/0 AWG | 53.5 | 105,600 | 0.122 | 0.201 | 125 / 150 A |
| 2/0 AWG | 67.4 | 133,100 | 0.0967 | 0.159 | 145 / 175 A |
| 3/0 AWG | 85 | 167,800 | 0.0766 | 0.126 | 165 / 200 A |
| 4/0 AWG | 107 | 211,600 | 0.0608 | 0.1 | 195 / 230 A |
| 250 kcmil | 127 | 250,000 | 0.0515 | 0.0847 | 215 / 255 A |
| 300 kcmil | 152 | 300,000 | 0.0429 | 0.0707 | 240 / 285 A |
| 350 kcmil | 177 | 350,000 | 0.0367 | 0.0605 | 260 / 310 A |
| 400 kcmil | 203 | 400,000 | 0.0321 | 0.0529 | 280 / 335 A |
| 500 kcmil | 253 | 500,000 | 0.0258 | 0.0424 | 320 / 380 A |
Calculate residential electrical service requirements using NEC methods
Box volume from conductors, devices, clamps and grounds, checked against NEC 314.16
Liquid and suction line sizes, extra charge per foot and a chart for R-410A, R-32 and R-454B
Wire gauges, circuit breaker sizes, electrical codes, and safety guidelines
Visual guide identifying standard North American plug configurations and their usage
NEC 2023 bathroom rules with section numbers, a does-it-need-GFCI checker and a one-or-more circuit planner