NEC 2017 to 2023 rules for outlets, AFCI, lighting and smoke alarms, with an outlet layout calculator and a printable inspection checklist.
Same bedroom rules again. Check local amendments: some states delay or trim AFCI requirements.
Your building department enforces one edition, sometimes with amendments. Call or check its website before you buy breakers.
Measure each stretch of wall along the floor between doors, closets and other openings. Walls 2 ft and wider count.
4 receptacles minimum
Save this bedroom plan to Blueprint: track the permit, the materials list (AFCI breaker, tamper-resistant receptacles, cable) and the inspection checklist on your phone.
45 ft of wall in 4 runs needs at least 4 receptacles under the 6 ft rule (NEC 210.52(A)), all tamper-resistant, on an AFCI-protected circuit (210.12(A)), with a switched light at the door and a smoke alarm.
Check the permit and your code edition
New circuits and added outlets are usually permitted work. Ask which NEC edition your town enforces and whether it amends the AFCI rules.
Lay out receptacles
Mark at least 4 receptacles so no point along the floor line is more than 6 ft from one; count every wall 2 ft or wider. Put extras where the bed and desk will go.
Plan lighting and the switch
A wall switch at the entry controls a ceiling light or a switched receptacle (210.70(A)(1)). Use a fan-rated box for a ceiling fan.
6 steps · 5 tools · 7 materials
3 more steps, the full tool list and a shopping list you can check off as you go.

Your plan is 60% built. Save it.
3/5Wire a bedroom: 4 receptacles on an AFCI circuit
Finished in 1 weekend · $242 DIY
Built for your receptacles of 4. Your first plan saves free. No card needed.
Or save it with just your email
We send a link; open it and this plan is your first project. Your first plan saves free. No card needed.
| Item | AFCI? | Code | Note |
|---|---|---|---|
| Receptacle | Yes | 210.12(A) | Combination AFCI breaker, or a listed AFCI receptacle first on the run where allowed |
| Ceiling light | Yes | 210.12(A) | A lighting outlet is an outlet; the whole circuit is protected |
| Ceiling fan | Yes | 210.12(A) | Same circuit rule as the light |
| Smoke alarm (hardwired) | Yes | 210.12(A) | If it is on a bedroom circuit; AFCI is not a reason to leave it off |
| Switched receptacle | Yes | 210.12(A), 210.70(A)(1) Ex. 1 | Can replace the ceiling light as the required switched lighting outlet |
| 240 V baseboard heater or window AC | No | 210.12(A) | The rule covers 120 V, 15 and 20 A circuits only |
| AFCI type | Cost | Use it |
|---|---|---|
| Combination AFCI breaker | $40 to $60 | Protects the whole circuit from the panel; the default for new circuits |
| Dual-function (AFCI and GFCI) breaker | $50 to $70 | Where a circuit needs both, such as a bedroom circuit that also feeds a laundry or wet bar receptacle |
| Outlet branch circuit (AFCI receptacle) | $35 to $45 | First outlet on an existing circuit when you extend or replace (210.12(D)); also for older panels with no AFCI breaker |
| Rule | Requirement | Code |
|---|---|---|
| Receptacle spacing | No point along the floor line more than 6 ft from a receptacle; every wall space 2 ft or wider counts | 210.52(A) |
| AFCI | All 120 V, 15 and 20 A circuits feeding outlets or devices in the bedroom | 210.12(A) |
| Extending a circuit | Add AFCI (breaker or first-outlet device) when extending or modifying a bedroom circuit more than 6 ft | 210.12(D) |
| Replacing a receptacle | A replacement where AFCI is now required must be AFCI-protected (AFCI receptacle or breaker) | 406.4(D)(4) |
| Tamper-resistant | All 15 and 20 A, 125 V receptacles; except those more than 5.5 ft above the floor | 406.12 |
| Switched lighting | A wall switch at the entry controlling a ceiling light or a switched receptacle | 210.70(A)(1) |
| Smoke alarms | In each bedroom, outside each sleeping area and on every level; hardwired and interconnected in new work | IRC R314 |
| CO alarms | Outside each sleeping area where there is a fuel-burning appliance or an attached garage | IRC R315 |
| GFCI | Not required for bedroom receptacles, except within 6 ft of a sink | 210.8(A) |
Enclosed LED fixtures at least 6 in. from the storage space, 12 in. for surface incandescent; no pendants or bare lamps (410.16).
Size the wire for long runs with the voltage drop calculator and check the panel with the electrical load calculator. For GFCI contrasts see the kitchen and bathroom electrical code sheets; for a fan, the ceiling fan installation guide.
Job checklist
Ticks are saved in this browser. A project keeps them on every device.
Ask about your situation. Posting needs a free account, and your question carries over so you get an answer with your project in view. Questions we hear often get answered on this sheet.
Pick one for a step-by-step plan with tools, materials and costs, or tell us in your own words.
Calculate residential electrical service requirements using NEC methods
Voltage drop and wire size for 120V, 240V, 3-phase and low-voltage DC runs
Box volume from conductors, devices, clamps and grounds, checked against NEC 314.16
NEC 2023 bathroom rules with section numbers, a does-it-need-GFCI checker and a one-or-more circuit planner
Circuit requirements, GFCI placement, appliance wiring, and outlet spacing for kitchen electrical work
Fan size, mount and downrod calculator, wiring diagrams for every switch setup, step-by-step install with times, and FAQs